Monday, 15 December 2014

Fabric ducting washing instruction.

Most of the fabric diffusers are made of high-quality resistant materials without a natural fibre admixture.
The used material is specified when your order is technically processed.The diffusers made of permeable fabric can be washed in a common industrialwashing machine.
Impermeable fabrics require a gentle mode washing, Certain fabric duct materials required hand washing only. If the washed diffuser has tyres (structure inside)

, braces or turn-buckles, these solid elements must be removed before the washing process. Induction surface dirt can bevacuumed, washing is unnecessary.

The process of washing:

Strictly follow the maintenance symbols indicated on the labels sewn near the zips in the
diffusers.

1. Wash the diffusers with common detergents (dosing according to the directions for use), the effect
of washing is enhanced if the diffuser is turned inside out. We advise you to repeat the washing up
to four times acc. to level of contamination, A special
detergent (we will recommend one by request according to the particular dirt) should be used if the
fabric is badly soiled.

2. Use a disinfectant only if it is essential according to the local service instructions. The chemical
composition of the disinfectant must not harm the diffuser fabric (see maintenance symbols).
Observe the producer`s dosing instructions.

3. Rinse the diffusers in clean water.

4. Spin-dry the diffusers gently, install them and finish drying by the air flow from the ventilator.


Below are the common symbol for fabric ducting washing instructions.



Thursday, 13 November 2014

Prinsip Asas Fabric Ducting (Sesalur udara jenis fabrik)


Fabric duct basic principle

Konsep fabric ducting agak berbeza dengan Konvensional ducting (Gi sheet duct, Pre insulated duct, Spiral duct). Konventional duct menggunakan konsep high velocity manakala fabric duct menggunakan konsep low velocity. Menurut hukum termodinamik, udara sejuk lebih berat dari udara panas. Cuba bayangkan jika air distribution menggunakan hukum alam semulajadi. Kita tidak perlu mengarahkan udara sejuk ke direction tertentu. Kita hanya meletakkan udara ditempat yang betul, kemudian kita hanya biarkan udara sejuk tersebut mengalir ke tempat yang sepayutnya. Mengikut hukum alam, udara sejuk lebih berat dari udara panas. Alangkah selesanya jika berada didalam yang pegerakan udaranya <0.3m/s. Spesifikasi di negara europe, angin yang bergerak dalam satu ruangan tidak boleh lebih dari 0.3m/s bagi mengelakkan cold draft syndrom yang boleh membahayakan kesihatan.

Oleh itu jika delta T (perbezaan suhu) antara suhu bilik dan suhu yang keluar dari fabric duct > 9F maka flow pattern seperti fig 4. Uadara sejuk akan jatuh dengan laju kebawah mungkin melebihi 0.3m/s. 

Jika perbezaan suhu bilik dan suhu udara yang keluar dari fabric duct <4F, maka flow pattern seperti fig 2. Dimana jika tiada perbezaan suhu ia dipanggil isothermal process. Disini menunjukkan perbezaan yang besar antara fabric duct & konventional duct. Dimana penggunaan fabric duct lebih selesa jika dibandingkan dengan konvensional sistem.





Bagi menghasilkan satu design sistem fabrik ducting yang baik, ada beberapa parameter perlu diambil kira. Antaranya :

1) Jenis aplikasi penggunaan penyaman udara
2) Ketinggian bilik
3) Air flow AHU/FCU
4) Interior design (Rekaan dalaman bilik)
5) External static pressure
6) Sound level yang dibenarkan
7) Warna fabrik yang akan digunakan


Fabric Duct 'POPING' sound eleminate by using soft starter for motor blower


Before blower motor using soft starter
After blower motor install soft starter





Tuesday, 28 October 2014

Bagaimana untuk design FABRIC DUCTING?

Disini saya ingin berkongsi info berkenaan cara untuk design atau sizing fabric ducting..

Normal praktis utk design gi duct, designer selalu menggunakan duct calculator. Dengan menetapkan parameter friction loss :

 # 0.1in wg - friction loss - 100ft duct run bagi supply duct.
# 0.08in wg - friction loss - 100ft duct run bagi return duct.

GI DUCT CALCULATOR


Bagi fabric ducting pula parameter yg ditetapkan ialah inlet velocity.

# 4 - 7 m/s utk Half Round duct.
# 5 - 8m/s utk Round Duct

Bagi memudahkan saya sertakan jadual bagi mendapatkan saiz fabric yang ideal tidak terlalu besar & tidak terlalu kecil..

Parameter tersebut ditetapkan bagi mengelakkan :
* pressure drop yang terlalu tinggi
* Mengelakkan terbulance
* Mengelakkan bunyi bising, fabric vibration
* penggunaan fabric secara berlebihan yg blh merugikan cost & ruang.

Selamat mencuba.. jika ada penambahbaikan sila comment dan saya akan betulkan..

Jika ada permasalahan boleh hubungi saya ditalian 03-51217258 / 0127438547. Saya sedia membantu bagi yang berminat.


Fabric duct calculator - Half round shape

Fabric duct calculator - Round shape


Fabric duct calculator - Round shape


Link
http://www.prihoda.com/my

https://www.facebook.com/prihodamalaysia

Mail Subscribe Box By MailChimp

Subscribe to our mailing list

* indicates required